![BENSHAW RSi GM2 Series Instruction Manual Download Page 107](http://html1.mh-extra.com/html/benshaw/rsi-gm2-series/rsi-gm2-series_instruction-manual_2735262107.webp)
Learning Advanced Features
890054-00-00
GM2 Series VFD
97
Setting*
Calculating final reference frequency
0
M[Hz]+(G[%]*A[Hz])
30 Hz(M)+(50%(G)x24 Hz(A))=42 Hz
1
M[Hz]*(G[%]*A[%])
30 Hz(M)x(50%(G)x40%(A))=6 Hz
2
M[Hz]/(G[%]*A[%])
30 Hz(M)/(50%(G)x40%(A))=150 Hz
3
M[Hz]+{M[Hz]*(G[%]*A[%])}
30 Hz(M)+{30[Hz]x(50%(G)x40%(A))}=36 Hz
4
M[Hz]+G[%]*2*(A[%]-50[%])[Hz]
30 Hz(M)+50%(G)x2x(40%(A)
–
50%)x60 Hz=24 Hz
5
M[HZ]*{G[%]*2*(A[%]-50[%])
30 Hz(M)x{50%(G)x2x(40%(A)
–
50%)} = -3 Hz(Reverse)
6
M[HZ]/{G[%]*2*(A[%]-50[%])}
30 Hz(M)/{50%(G)x2x(60%
–
40%)} = -300 Hz(Reverse)
7
M[HZ]+M[HZ]*G[%]*2*(A[%]-50[%])
30 Hz(M)+30 Hz(M)x50%(G)x2x (40%(A)
–
50%)=27 Hz
*
M: Main frequency reference/ G: Auxiliary reference gain (%)/ A: Auxiliary frequency
reference (Hz or rpm) or gain (%)
Auxiliary Reference Operation E.g. #3
V1 is Main Frequency and I2 is Auxiliary Frequency
•
Main frequency: V1 (frequency command setting to 5 V and is set to 30 Hz)
•
Maximum frequency setting (dr.20): 400 Hz
•
Auxiliary frequency (bA.01): I2[Display by percentage (%) or auxiliary frequency (Hz) depending on
the operation setting condition]
•
Auxiliary reference gain (bA.03): 50%
•
In.01-32: Factory default output
Example: an input current of 10.4 mA is applied to I2, with the frequency corresponding to 20 mA of
60 Hz. The table below shows auxiliary frequency A as 24 Hz(=60[Hz]x{(10.4[mA]-4[mA])/(20[mA]-
4[mA])} or 40%(=100[%] x {(10.4[mA] - 4[mA]) /(20 [mA] - 4[mA])}.
Setting*
Calculating final reference frequency
0 M[Hz]+(G[%]*A[Hz])
30 Hz(M)+(50%(G)x24 Hz(A))=42 Hz
1 M[Hz]*(G[%]*A[%])
30 Hz(M)x(50%(G)x40%(A))=6 Hz
2 M[Hz]/(G[%]*A[%])
30 Hz(M)/(50%(G)x40%(A))=150 Hz
3 M[Hz]+{M[Hz]*(G[%]*A[%])}
30 Hz(M)+{30[Hz]x(50%(G)x40%(A))}=36 Hz
4 M[Hz]+G[%]*2*(A[%]-50[%])[Hz]
30 Hz(M)+50%(G)x2x(40%(A)
–
50%)x60 Hz=24 Hz
5 M[HZ]*{G[%]*2*(A[%]-50[%])}
30 Hz(M)x{50%(G)x2x(40%(A)
–
50%)}=-3 Hz(Reverse)
6 M[HZ]/{G[%]*2*(A[%]-50[%])}
30 Hz(M)/{50%(G)x2x(60%
–
40%)}=-300 Hz(Reverse)
7
M[HZ]+M[HZ]*G[%]*2*(A[%]-50[%]) 30 Hz(M)+30 Hz(M)x50%(G)x2x(40%(A)
–
50%)=27 Hz
*
M: Main frequency reference/ G: Auxiliary reference gain (%)/ A: Auxiliary frequency
reference (Hz or rpm) or gain (%)
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...