Learning Advanced Features
890054-00-00
GM2 Series VFD
143
Note
Press regeneration prevention only operates during constant motor speed operation and
does not operate during accelerations or decelerations. When regeneration prevention is
activated, output frequency may change within the range set at Ad.76 (CompFreq Limit).
Analog output
The analog output terminal (AO) provides an output of 0
–
10 VDC. The analog output can
represent one of a variety of signals. Scaling and filtering can also be applied to the signal.
Voltage Analog Output
Group Code
Name
Setting
Setting Range
Unit
OU
01 Analog output 1 item 0
Frequency
0
–
15
-
02 Analog output 1 gain 100.0
-1000.0
–
1000.0
%
03 Analog output 1 bias 0.0
-100.0
–
100.0
%
04 Analog output 1 filter 5
0
–
10000
ms
05
Analog constant
output1
0.0
0.0
–
100.0
%
06
Analog output1
monitor
0.0
0.0
–
1000.0
%
Voltage Analog Output Setting Details
Code and
Features
Description
OU.01
AO1
Mode
Select a type of signal to output.
Configuration Function
0
Frequency AO output voltage based on operating
frequency. Outputs 10V at the frequency set at
dr.20 (Max Freq).
1
Output
Current
AO output voltage based on inverter output
current. Outputs 10V at 200% of inverter rated
current (heavy load).
2
Output
Voltage
AO output voltage based on inverter output
voltage. Outputs 10 V at the voltage set in bA.15
(Motor Rated Voltage). If 0 V is set in bA.15, 10 V
is based on the actual input voltage.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...