Learning Advanced Features
890054-00-00
GM2 Series VFD
109
Group Code
Name
Setting
Setting Range
Unit
34
PID controller
motion frequency
0.00
0
–
Max
Frequency
Hz
35
PID controller
motion level
0.0
0.0
–
100.0
%
36
PID controller
motion delay time
600
0
–
9999
sec
37
PID sleep mode
delay time
60.0
0
–
999.9
sec
38 PID sleep mode frequency
0.00
0
–
Max
Frequency
Hz
39 PID wake-up level
35
0
–
100
%
40 PID wake-up mode selection 0 Below Level
0
–
2
-
43 PID unit gain
100.0
0
–
300
%
44 PID unit scale
2 x 1
0
–
4
-
45 PID 2
nd
proportional gain
100.00
0
–
1000
%
In
65~69
Px terminal setting options
22 I-Term Clear
0
–
52
-
23
PID
Openloop
24 P Gain2
PID Basic Operation Setting Details
Code and
Features
Description
AP.01 App Mode
Set to 2 (Proc PID) to enable PID Control and select functions for the
process PID.
AP.16 PID Output
Displays the existing output value of the PID controller. The gain and
scale that were set at AP.43, 44 are applied on the display.
AP.17 PID Ref
Value
Displays the existing reference value set for the PID controller. The
gain and scale that were set at AP.43, 44 are applied on the display.
AP.18 PID Fdb
Value
Displays the latest feedback value as input to the PID controller. The
gain and scale that were set at AP.43, 44 are applied on the display.
AP.19 PID Ref Set
When AP.20 (PID reference source) is set to 0 (Keypad default), the
reference value is entered here, AP.19. If the reference source (AP.20)
is set to any other source, the setting values for AP.19 are void.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...