RS-485 Communication Features
201
890054-00-00
GM2 Series VFD
Comm.
Address
Parameter
Scale Unit
Changeable
During
Operation
Function
Read: 0: Unlock, 1: Lock
0h03E8
Lock parameter mode
0
Hex
O
Write: 0
–
9999
Read: 0: Unlock, 1: Lock
0h03E9
Reserved
-
-
-
Reserved
0h03EA
Initializing power
consumption
-
-
O
0: No, 1: Yes
0h03EB
Initialize inverter
operation accumulative
time
-
-
O
0: No, 1: Yes
0h03EC
Initialize cooling fan
accumulated operation
time
-
-
O
0: No, 1: Yes
Note
When setting parameters in the inverter memory control area, the values are
reflected to the inverter operation and saved. Parameters set in other areas via
communication are reflected in the inverter operation, but are not saved. All set
values are cleared following an inverter power cycle. Therefore, changes made via
communications to Common Area parameters must be saved before turning off the
inverter. Set parameter dr.92 to 1 (Parameter Save).
•
Define the parameter carefully. After setting a parameter to 0 via communication,
set it to another value. If a parameter has been set to a value other than 0 and a
non-zero value is entered again, an error message is returned. The previously-set
value can be identified by reading the parameter when operating the inverter via
communication.
•
The addresses 0h03E7 and 0h03E8 are parameters for entering the password. When
the password is entered, the condition will change from Lock to Unlock, and vice
versa. When the same parameter value is entered continuously, the parameter is
executed just once. Therefore, if the same value is entered again, change it to
another value first and then re-enter the previous value.
For example, if you want to enter 244 twice, enter it in the following order: 244
→
0
→
244.
It may take longer to set the parameter values in the inverter memory control area
because all data is saved to the inverter. Communication may be lost during parameter
setup if parameter setup is continues for an extended period of time.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...