64
GM2 Series VFD
890054-00-00
Learning Basic Features
Setting RS-485 Communications as a Command Input Device
Set drv (command source) to 3 (Int 485). Control the inverter with upper-level controllers (PCs or
PLCs) via RS-485 communications using the (S+/S-) input terminals of the control board. Refer to
Group Code
Name
Setting
Setting Range Unit
Operation drv Command Source
3 Int 485
0
–
4
-
CM
01
Built-in communication
inverter ID
1
1
–
250
-
02
Built-in communication
protocol
0 ModBus RTU
0
–
2
-
03
Built-in communication
speed
3 9600 bps
0
–
7
-
04
Built-in communication
frame setting
0 D8/PN/S1
0
–
3
-
Forward or Reverse Run Prevention
The rotation direction can be configured to prevent motors from rotating in a specific direction. Set
Ad.09 to prevent rotation in either the Fwd or Rev direction.
Group Code
Name
Setting
Setting Range Unit
Ad
09
Run prevention
options
0 None
0
–
2
-
1 Forward Prev
2 Reverse Prev
Forward/Reverse Run Prevention Setting Details
Code and
Features
Description
Ad.09
Run Prevent
Choose a direction to prevent.
Configuration
Function
0
None
Do not set run prevention.
1
Forward Prev
Set forward run prevention.
2
Reverse Prev
Set reverse run prevention.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...