Learning Advanced Features
890054-00-00
GM2 Series VFD
127
Energy Saving Operation
Manual Energy Saving Operation
When the inverter output current is lower than the current which is set at bA.13 (Motor Rated
Current), the output voltage is reduced by the percentage set in Ad.51 (Energy Save). The voltage
before the energy saving operation starts will become the base value of the percentage. Manual
energy saving operation will not be carried out during acceleration and deceleration.
Group Code
Name
Setting
Setting
Range
Unit
Ad
50
Energy saving
operation
1
Manual
-
-
51
Energy saving
amount
30
0
–
30
%
Automatic Energy Saving Operation
The amount of energy saving can be automatically calculated based on the rated motor current
(bA.13) and the no-load current (bA.14). From the calculations, the output voltage can be adjusted.
Group Code
Name
Setting
Setting Range
Unit
Ad
50
Energy saving
operation
2
Auto
-
-
The inverter will exit the energy saving mode, when the reference frequency is changed or
during acceleration and deceleration. The actual Acc/Dec time may take longer than the
set Acc/Dec time due to the time required to return to normal operation.
Output Voltage
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...