RS-485 Communication Features
890054-00-00
GM2 Series VFD
200
Comm.
Address
Parameter
Scale
Unit
Assigned Content by Bit
B1
Relay 2 (0.4
–
7.5 kW, OU.33: None)
B0
Relay 1 (0.4
–
7.5 kW, OU.31: None)
0h0387
Reserved
-
-
Reserved
0h0388
PID reference
0.1
%
PID reference command
0h0389
PID feedback value
0.1
%
PID feedback value
0h038A
Motor rated current
0.1
A
-
0h038B
Motor rated voltage
1
V
-
0h038C
–
0h038F
Reserved
-
-
Reserved
0h0390
Torque Ref
0.1
%
Torque command
0h0391
Fwd Pos Torque Limit
0.1
%
Forward motoring torque limit
0h0392
Fwd Neg Torque Limit
0.1
%
Positive-direction regeneration torque limit
0h0393
Rev Pos Torque Limit
0.1
%
Reverse motoring torque limit
0h0394
Rev Neg Torque Limit
0.1
%
Negative-direction regeneration torque limit
0h0395
Torque Bias
0.1
%
Torque bias
NOTE: A frequency set via communication using the common area frequency address
(0h0380, 0h0005) is not saved even when used with the parameter save function. To save a
changed frequency to use after a power cycle, follow these steps:
Set a frequency reference after setting the frequency reference source to 1
(Keypad-1).
Set the frequency via communication into the parameter area frequency address
(0h1D04).
Perform the parameter save (0h03E0: '1') before turning off the power. After the
power cycle, the frequency set before turning off the power is displayed.
Memory Control Area Parameter (Read and Write)
Comm.
Address
Parameter
Scale Unit
Changeable
During
Operation
Function
0h03E0
Save parameters
-
-
X
0: No, 1: Yes
0h03E1
Monitor mode
initialization
-
-
O
0: No, 1: Yes
0h03E2 Parameter initialization
-
-
X
0: No, 1: All Grp, 2: Drv Grp
3: bA Grp, 4: Ad Grp, 5: Cn Grp
6: In Grp, 7: OU Grp, 8: CM Grp
9: AP Grp, 12: Pr Grp, 13: M2 Grp,
14: Operation group
Setting is prohibited during fault
interruptions.
0h03E3
Changed parameter
display
-
-
O
0: No, 1: Yes
0h03E4
Reserved
-
-
-
Reserved
0h03E5
Delete all fault history
-
-
O
0: No, 1: Yes
0h03E6
Delete user-registrated
codes
-
-
O
0: No, 1: Yes
0h03E7
Hide parameter mode
0
Hex
O
Write: 0
–
9999
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...