GM2 Series VFD
890054-00-00
Learning Basic Features
Multi-step Frequency Configuration
Multi-step operations (Fixed Speed Inputs) can be assigned to the Px terminals. Step 0 uses the
frequency reference source set with Frq in the Operations group. Steps 1 through 7 can be
configured using (3) digital input terminals. Set Px terminals to 7 (Speed-L), 8 (Speed-M) and 9
(Speed-H). These are recognized as binary inputs (000 ~ 111) and work in combination with Fx or
Rx run commands. The inverter operates according to the frequencies set with parameters St1, St2
and St3 (step frequencies 1~3) and bA.53 ~ bA.56 (step frequencies 4
–
7). and the binary command
combinations.
Multi-step Frequency Settings
Group
Code
Name
Setting
Setting Range
Unit
Operation St1~St3
Multi-step
frequency 1
–
3
-
0
–
Max Frequency
Hz
bA
53
–
56
Multi-step
frequency 4
–
7
-
0
–
Max Frequency
Hz
In
65
–
69
Px terminal
setting options
7 Speed-L
0
–
52
-
8 Speed-M
-
9 Speed-H
-
89
Multi-step
command delay
time
1
1
–
5000
ms
Multi-step Frequency Setting Details
Code and
Features
Description
Operation group
St1~St3
Configure multi-step frequencies 1
–
3.
bA.53 ~ bA
–
56
Step Freq 4
–
7
Configure multi-step frequencies 4
–
7.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...