![BENSHAW RSi GM2 Series Instruction Manual Download Page 266](http://html1.mh-extra.com/html/benshaw/rsi-gm2-series/rsi-gm2-series_instruction-manual_2735262266.webp)
Technical Specification
890054-00-00
256
GM2 Series VFD
Items
Description
• acc/dec/stop
• Exit PID Operation
Output
Multi-
function
relays
Programmable Output Relays
AC 250 V, 1 A
DC 30V, 1A
Relay 1 (A1-C1-B1)
Relay 2 (A2-C2)
Analog
output
0
–12 VDC: Programmable Analog Output
Protection
Trip
• Motor Overload
• Under Torque
• Motor Under Load
• Inverter Over Heat
• Over Current (OC1)
• Short Circuit (OC2)
• Over Voltage
• External Trip
• Low Voltage
• Hardware Fault
• Ground Fault
• Temperature Sensor (NTC)
• Motor Over Heat (Eth)
• Fan Fault
• Phase Open (In/Out)
• Pre-PID Operation Failure
• Inverter Overload
• External Brake Trip
• No Motor Trip
• Reference Loss
• Over Torque
• Option Board trip
Alarm
Warnings:
Reference Loss, Motor Overload, Motor Under Load,
Inverter Overload, Fan, Dynamic Braking Rate Warning, Auto
Tuning Error, Inverter Overheat
Instantaneous
Power Outage
Normal Duty: Less the 8ms (~1/2 cycle)
Heavy Duty: Less than 15 ms (~ 1 cycle)
For longer outages use KEB operation and/or Auto Restart
operation
Structure /
Working
Environment
Cooling type
Forced fan cooling structure
Protection
structure
IP 20, UL Open Type
UL Enclosed Type 1 is achieved with conduit box installation
(option)*
Ambient
Operating
temperature
14
°
F ~ +104
°
F (-10
°
C ~ +40
℃
)
Derating: 2% output amps for every degree above 104
°
F (40
°
C),
maximum 122°F (50
°
C)
No ice or frost should be present
Ambient humidity
Less than 95% RH (avoid condensation forming)
Storage
temperature
-4
°
F ~ +149
°
F (-20
℃
~ +
65
℃
)
Environmental
factors
Prevent contact with corrosive gases, inflammable gases, oil
stains, dust, and other pollutants (Pollution Degree 2 Environment).
Operation
altitude/vibration
3280 ft (1,000 m).
Apply derating of 1% voltage/output current for every 100 m above
1,000 m, maximum of 4,000 m
Less than 9.8 m/sec
2
(1G).
Air pressure
15 PSI (70 ~106 kPa)
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...