Learning Advanced Features
890054-00-00
GM2 Series VFD
123
Problem
Relevant
Function Code
Troubleshooting
If low speed (3 Hz or
less) out-of-phase
occurs because the
inertia of load is high.
Cn.30 Spd.
Response
Adjustment Gain
Sometimes control is not possible under a low
speed due to high load inertia. In this case,
increase the Cn.30 value by 1 unit at a time.
If motor rotation count
error margin occurs
during no load
Cn.29 Spd. Comp.
Gain at No-load
If over 10 RPM of motor rotation count error
occurs during no load operation, adjust the
Cn.29 value by 0.01 unit at a time.
If speed response is
required
Cn.30
Spd.Response
Adjustment Gain
Although the speed response is improved the
greater the Cn.30 value, speed control may
become unstable. Excessive setup may cause
an inverter trip.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...