Learning Basic Features
81
Lea
rni
890054-00-00
GM2 Series VFD
Group Code
Name
Setting
Setting Range
Unit
13
Amount of applied
DC
50
0-Rated Current of
Inverter/Rated
Current of Motor x
100%
%
The amount of DC braking required is based on the motor’s rated current. If the DC
braking current is too high or brake time is too long, the motor may overheat or be
damaged. The maximum amount of applied DC current is limited to the inverter rated
current.