Learning Advanced Features
890054-00-00
GM2 Series VFD
151
Trip Output to Multi-function (digital) relay
With Relay1 or Relay2 set to 29 (Trip), OU.30 (Fault Output) can further define relay activation
during low voltage faults, all faults and auto restart functions. Additionally, On and Off time delays
can also be applied specifically to a relay when set to 29 (Trip).
Group Code
Name
Setting
Setting Range
Unit
OU
30 Fault output item
010*
-
bit
31
Multi-function (digital)
relay1 item
29 Trip
-
-
33
Multi-function (digital)
relay2 item
14 Run
-
-
53 Fault output On delay
0.00
0.00
–
100.00
sec
54 Fault output Off delay
0.00
0.00
–
100.00
Sec
* Displayed as
on the keypad.
Trip Setting Details to Multi-function (digital) relay
Code and
Features
Description
OU.30 Trip Out
Mode
Bit On/Off representation on display.
Items
Bit On Status
Bit Off Status
Keypad
Set OU.31 (Relay1) or OU.33 (Relay2) to 29 (Trip). When a fault
occurs, the relay will be activated. Relay activation can be set based
on trip type per the table below.
Configuration
Function
bit3
bit2
bit1
✓
Operates when low voltage faults occur
✓
Operates when all faults other than low
voltage occur
✓
Operates when auto restart fails (Pr. 08
–
09)
010 Displayed as
on the keypad.
OU.31 Relay1
Configure Relay 1 output function.
OU.33 Relay2
Configure Relay 2 output function.
OU.53 TripOut On
Dly, OU.54 TripOut
OffDly
When a trip occurs, the relay (Relay1 or Relay2) will be activated
after the delay time set in OU.53 (On Dly). After a reset, the relay will
be initialized after the delay time set in OU.54 (Off Dly).
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...