![BENSHAW RSi GM2 Series Instruction Manual Download Page 32](http://html1.mh-extra.com/html/benshaw/rsi-gm2-series/rsi-gm2-series_instruction-manual_2735262032.webp)
Installing the Inverter
22
GM2 Series VFD
890054-00-00
Pre-insulated Crimp Terminal
Use pre-insulated crimp terminal connectors to increase reliability of the control terminal wiring.
Refer to the specifications below to determine the crimp terminals to fit various cable sizes.
* If the length (L) of the crimp
terminals exceeds 0.5” (12.7mm) after wiring, the control terminal
cover may not close fully.
Wired connection to control terminals
To connect cables to the control terminals without using crimp terminals, refer to the following
illustration detailing the correct length of exposed conductor at the end of the control cable.
Cable
Spec.
Dimensions (inches/mm)
AWG mm
2
L*
P
d1
D
22 0.50 0.4/12.0 0.2/6.0 0.05/1.3 0.13/3.2
20 0.75 0.4/12.0 0.2/6.0 0.06/1.5 0.13/3.4
18
1.0 0.4/12.0 0.2/6.0 0.07/1.7 0.14/3.6
Note
•
While making wiring connections at the control terminals, ensure that
the total cable length does not exceed 165 ft (50 m).
•
Ensure that the length of any safety related wiring does not exceed 100
ft (30m).
•
Use ferrite material to protect signal cables from electro-magnetic
interference.
•
Take care when supporting cables using cable ties, to apply the cable
ties no closer than 6 inches from the inverter. This provides sufficient
access to fully close the front cover.
•
When making control terminal cable connections, use a small flat-tip
screw driver (0.1 in wide (2.5 mm) and 0.015 in thick (0.4 mm) at the tip).
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...