Fire Mode Operation
Fire Mode operation is for use in emergency situations. When enabled, Fire Mode allows the
inverter to provide continuous operation ignoring the majority of faults. Primarily used for fire
pump operation, but can be applied when continuous operation is required due to emergencies.
When enabled, Fire mode forces the inverter to ignore all minor faults and repeats a Reset/Restart
of major faults, regardless of the Reset/Restart count limit.
Fire
Mode Parameter Settings
Group Code
Name
Setting
Setting
Range
Unit
Ad
80
Fire Mode selection
0 None
0
–
2
-
1 Fire Mode
2 Fire Mode
Test
81
Fire Mode frequency 60
0
–
60
82
Fire Mode run
direction
0
Fwd
0
–
1
1
Rev
83
Fire Mode operation
count
Not
configurable
-
-
In
65~69 Px terminal setting
options
51 Fire Mode
0
–
52
-
Fire
Mode Parameter Settings Details
Code
Description
Details
Ad.80
Fire mode
selection
When set to 1 (Fire Mode), enables Fire Mode operation
controlled with a digital input. When set to 2 (Fire Mode
Test), allows testing of Fire Mode operation.
Ad.81 Fire
Mode
frequency
Fire mode
frequency
reference
The frequency set at Ad. 81 (Fire mode frequency) is used
for the inverter operation in Fire mode. The Fire mode
frequency takes priority over the Jog frequency, Multi-step
frequencies, and the keypad input frequency.
Ad.82
Fire Mode Run
direction
Set the direction of motor rotation during Fire Mode
operation.
Ad.83
Fire Mode
count
Counts the number of Fire Mode operations. Does not
increase count during Fire Mode testing.
ACC
Acc Time
Dec
Dec Time
Fire mode
Acc/Dec times
During Fire Mode operation, the inverter accelerates and
decelerates based on the times set in ACC and Dec
parameters. When the Px terminal in activated, the inverter
accelerates based on the time set in ACC. When the Px
terminal is de-activated, the inverter decelerates based on
the time set in Dec.
In.65~In.69
Px terminal
Px terminal
setting
Set to 51 (Fire Mode). When the digital input is activated,
the inverter will operate in Fire Mode.
Summary of Contents for RSi GM2 Series
Page 2: ...ii...
Page 58: ...48 GM2 Series VFD Perform Basic Operations 890054 00 00...
Page 122: ...Learning Advanced Features 112 890054 00 00 GM2 Series VFD PID control block diagram...
Page 188: ...Learning Protection Features 178 GM2 Series VFD 890054 00 00...
Page 279: ...Technical Specification 269 890054 00 00 GM2 Series VFD...