Section 5 - Wired Zone Expansion
5–3
Programming Wired Expansion Zones
Each zone must be programmed into the system using the
✱
56/
✱
58 Zone Programming mode,
which assigns characteristics that define the way the system responds to faults on that zone.
Refer to
Section 15: Zone Response Type Definitions
and
Section 17: Zone
Programming
for specific instructions on programming wired expansion zones.
Checkout Procedure for Wired Expansion Zones
Whenever it becomes necessary to disconnect power in order to add a module or keypad, always
disconnect the battery first, then the AC transformer. After installation has been completed,
connect the AC transformer first, then the battery.
After you have completed installation and programming of all devices, all expansion zones in
the security system should be checked as follows:
1. Make certain that all devices and sensors connected to the wired expansion zones are not
in a faulted state. Doors and windows with contacts should be closed, PIRs should be
covered (use a cloth to mask them temporarily, if necessary).
2. Plug in the AC transformer. With all zones intact (including hardwired zones), the alpha
keypad connected to the system should display:
✱✱✱✱
D I S A R M E D
✱✱✱✱
R E A D Y T O A R M .
If the following is displayed,
D I S A R M E D P r e s s
✱
t o s h o w f a u l t s
press
[
✱
]
to display the faulted zone(s). Restore any faulted zone(s) as necessary. Also
make sure that you have connected a 1000 ohm EOL resistor across the terminals of
unused expansion zones on the 4219 or 4229 Module.
When the
READY TO ARM
message is displayed, you can proceed to the next step.
3. Fault and restore every contact or sensor in each expansion zone individually to ensure
that it is being monitored by the system. Each time a zone is faulted, the keypad displays
the number of the faulted zone. When each zone is restored, the
READY TO ARM
message appears again.
Observe the keypad in each zone, as each zone is faulted and restored.
4. When the proper displays appear on the keypad(s), the wired expansion zones in the
system are functioning properly.
5. Unplug the AC transformer.
A
CHECK 09
message on the display signifies one of two problems:
•
Data from the control is not reaching the zone expander module. Check the wiring and DIP
switch settings.
or
•
The tamper jumper is on in the expansion module and the expansion module cover is off.
Summary of Contents for Vista-20Bay
Page 2: ......
Page 22: ...VISTA 20BAY Installation Setup Guide 3 4 ...
Page 28: ...VISTA 20BAY Installation Setup Guide 4 6 ...
Page 32: ...VISTA 20BAY Installation Setup Guide 5 4 ...
Page 40: ...VISTA 20BAY Installation Setup Guide 6 8 ...
Page 64: ...VISTA 20BAY Installation Setup Guide 14 4 ...
Page 68: ...VISTA 20BAY Installation Setup Guide 15 4 ...
Page 82: ...VISTA 20BAY Installation Setup Guide 16 14 ...
Page 92: ...VISTA 20BAY Installation Setup Guide 17 10 ...
Page 98: ...VISTA 20BAY Installation Setup Guide 18 6 ...
Page 100: ...VISTA 20BAY Installation Setup Guide 19 2 ...
Page 110: ...VISTA 20BAY Installation Setup Guide 22 4 ...
Page 116: ...VISTA 20BAY Installation Setup Guide 23 6 ...
Page 122: ...VISTA 20BAY Installation Setup Guide 25 4 NOTES ...
Page 128: ...VISTA 20BAY Installation Setup Guide A 2 ...
Page 130: ...VISTA 20BAY Installation Setup Guide B 2 ...
Page 138: ... 1 9 l N7526 4V1 5 00 SINCE 1946 BAY ALARM 925 Ygnacio Valley Road Walnut Creek CA 94596 ...