4–1
S E C T I O N 4
Basic Hardwired Zones 1–8
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
In This Section
♦
General Information
♦
Installing the Hardwired Zones
♦
Programming Hardwired Zones
♦
Checkout Procedure for Hardwired Zones
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • •
General Information
This section provides general information about the hardwired zones in the system, plus
specific instructions for installing 2-wire smoke detectors, 4-wire smoke/combustion
detectors, and 2-wire latching-type glassbreak detectors.
Installing the Hardwired Zones
Common Characteristics for Zones 1-8
• EOLR-supervised zones supporting both open circuit and closed circuit devices.
• As many 4-wire smoke detectors as can be powered from Aux Power on the control (zones
2-7).
• Programmable for 10, 350, or 700mSec response.
• 350mSec (default) should be used for most standard contacts. For vibration-type contacts,
10mSec is more suitable.
Wiring Burglary and Panic Devices to Zones 1
-
8
1. Connect sensors/contacts to the hardwired zone terminals (8 through 20). See
Figure 23.
VISTA-20BAY Summary of Connections
diagram.
2. Connect closed circuit devices in series in the high (+) side loop. The EOL resistor must be
connected in series with the devices, following the last device. See
Figure 23. VISTA-
20BAY Summary of Connections
diagram.
3. Connect open circuit devices in parallel across the loop. The 2,000-ohm EOLR must be
connected across the loop wires
at the last device.
If the EOLR is not at the end of the loop, the zone will not be properly supervised, and the system
may not respond to an open circuit on the zone.
High Resistance Supervision on Hardwired Zones 2-8
Special supervision in the control senses high resistance on hardwired zone loops 2-8,
causing a warning
CHECK
and the affected zone number to be displayed when the system is
in the disarmed state. The system cannot be armed when this display is present. If the
system is in the armed state when the high-resistance condition occurs, no such warning will
be displayed until the system is disarmed.
Summary of Contents for Vista-20Bay
Page 2: ......
Page 22: ...VISTA 20BAY Installation Setup Guide 3 4 ...
Page 28: ...VISTA 20BAY Installation Setup Guide 4 6 ...
Page 32: ...VISTA 20BAY Installation Setup Guide 5 4 ...
Page 40: ...VISTA 20BAY Installation Setup Guide 6 8 ...
Page 64: ...VISTA 20BAY Installation Setup Guide 14 4 ...
Page 68: ...VISTA 20BAY Installation Setup Guide 15 4 ...
Page 82: ...VISTA 20BAY Installation Setup Guide 16 14 ...
Page 92: ...VISTA 20BAY Installation Setup Guide 17 10 ...
Page 98: ...VISTA 20BAY Installation Setup Guide 18 6 ...
Page 100: ...VISTA 20BAY Installation Setup Guide 19 2 ...
Page 110: ...VISTA 20BAY Installation Setup Guide 22 4 ...
Page 116: ...VISTA 20BAY Installation Setup Guide 23 6 ...
Page 122: ...VISTA 20BAY Installation Setup Guide 25 4 NOTES ...
Page 128: ...VISTA 20BAY Installation Setup Guide A 2 ...
Page 130: ...VISTA 20BAY Installation Setup Guide B 2 ...
Page 138: ... 1 9 l N7526 4V1 5 00 SINCE 1946 BAY ALARM 925 Ygnacio Valley Road Walnut Creek CA 94596 ...