Object 1006
h
Communication cycle period
This object defines the SYNC interval. The value must be supplied as a multiple of µs. If the value is set to 0000
0000
h
the transmission of SYNC messages will be disabled.
7.1.6.
Object 1010
h
Store param eters
Use this object to save the customised settings such as Node ID, baud rate, etc. to the internal EEPROM. User
can store parameters in both NMT operational and pre-operational state.
Procedures:
An NMT request or a new power cycle is required to enable the stored settings.
7.1.7.
Object 1011
h
Restore fact ory default parameters
Use this object to restore the factory default values for the parameters of the communication profile, device profile
and application profile. The factory default values are specified in Table 8, Table 9 and the object dictionary
overview tables. Customised devices may have different factory default values, which may deviate from this
manual. See the datasheet of your customized product for these customized factory default values. You can
restore the factory default in both NMT operational and pre-operational state.
Procedures:
A direct NMT restart or new power cycle is required to enable the factory default settings after
a “load”. Do
not execute “save” before you restart the device, as this will cause the current working environment settings to
overwrite (i.e. store) the default factory settings.
Write "save" to
object 1010
h
NMT Reset or
New Power Cycle
Customised
value valid
Restore default
parameters
NMT Reset or
New Power Cycle
Default value
valid
▪
Write “load” to sub-index 01
h
= All parameters will be restored.
▪
Write “load” to sub-index 02
h
= Parameters of communication profile (Index from 1000
h
to 1FFF
h
) will be
restored.
▪
Write “load” to sub-index 03
h
= Parameters of application profile (Index from 6000
h
to 9FFF
h
) will be
restored.
▪
Write “load” to sub-index 04
h
= Parameters of manufacturer-specific profile (Index 2000
h
– 5FFF
h
) will be
restored.
▪
Write “load” in ASCII or “64616F6C
h
” have the same effect.
▪
Write “save” to sub-index 01
h
= All parameters will be stored.
▪
Write “save” to sub-index 02
h
= Parameters of communication profile (Index from 1000
h
to 1FFF
h
) will be
stored.
▪
Write “save” to sub-index 03
h
= Parameters of application profile (Index from 6000
h
to 9FFF
h
) will be
stored.
▪
Write “save” to sub-index 04
h
= Parameters of manufacturer-specific profile (Index from 2000
h
to 5FFF
h
)
will be stored.
▪
Write “save” in ASCII or “65766173
h
” have the same effect.
•