6–33
6.7.3 – Productivity3000 PLC Example Program (continued)
This rung compares 1 tag, “SoftStartTimeEntry”, to another tag, “OldSoftStartTime”. This allows the ladder to perform a sequence if the first tag
(assumed for example purposes to be coming from an HMI, but can also be changed from Data View). It will Copy the new value to the old value tag,
and then start the Write/Read confirmation sequence. When the value read from the soft starter is equal to the new entry, the sequence resets.
WriteReadTime
RST
SET
WriteReadTime
12
12.1
13
Enable
COPY DATA
Source
SoftStartTimeEntr
Destination
OldSoftStartTime
SoftStartTime
OldSoftStartTime
=
SoftStartTimeEntry
SoftStartTimeResult
=
SoftStartTimeEntry
Once the value read back from the unit is equal to the new value, the sequence is reset.
END
14
Chapter 6: Serial Communications
SR44 Series Soft Starter User Manual
1st Ed, Rev B 07/31/2019
Summary of Contents for Stellar SR44
Page 1: ...STELLAR SR44 SOFT STARTER USER MANUAL SR44 M WO 1st Edition Revision B...
Page 2: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 6: ...SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019 w 4 BLANK PAGE...
Page 8: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 12: ...Table of Contents BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019 t 4...
Page 23: ...ELECTRICAL INSTALLATION 2 CHAPTER CHAPTER 2 2 CHAPTER BLANK PAGE 2 1c...
Page 75: ...KEYPAD MENU ITEMS AND PARAMETERS CHAPTER 5 CHAPTER CHAPTER 5 BLANK PAGE 5 5 1c...
Page 237: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 238: ...SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...