5–77
5.4.12 – ‘Trips’ Menu (continued)
‘Trips’ Sub-menu of ‘Trips’ Menu
Last Trip (‘Trips’ sub-menu of ‘Trips’ menu)
‘Last Trip’ holds the number of the last trip.
2nd Last Trp (‘Trips’ sub-menu of ‘Trips’ menu)
‘2nd Last Trip’ holds the number of the second to last trip.
3rd Last Trp (‘Trips’ sub-menu of ‘Trips’ menu)
‘3rd Last Trip’ holds the number of the third to last trip.
4th Last Trp (‘Trips’ sub-menu of ‘Trips’ menu)
‘4th Last Trip’ holds the number of the fourth to last trip.
5th Last Trp (‘Trips’ sub-menu of ‘Trips’ menu)
‘5th Last Trip’ holds the number of the fifth to last trip.
Trip Sensitivity
Range: 1 to 15
Default: 1
Scaling: n/a
Type: R/W
‘Trip Sensitivity’ holds an arbitrary number to adjust the sensitivity of the fault trips of P-127,
‘Hidden Trip Flags’. The larger the setting of P-72, the slower the trips of P-127.
P126 Comms Trip
Range: 0 to 255
Default: 0
Scaling: n/a
Type: R/W
‘Bus Action on Fail’ – Action following a bus failure: (Active only with certain Comms Options.)
0 = No Trip; 1 = Trip.
Cooling
Range: P53 / B5
Default: On
Scaling: n/a
Type: R/W
This menu item turns ‘On’ and ‘Off’ the ‘Cooling’ function. Once this menu item has been turned
‘On’, and the unit has been started and subsequently stopped, the ‘Cooling’ function inhibits the
start command (not allowing the unit to start), until the time held in ‘Cooling Time’ has elapsed
(measured from the last stop signal). During this period the unit displays ‘Stopped. Cooling’. This
menu item is mainly for use in commissioning soft-start units that have large thyristor stacks, and
its purpose is to avoid damage to the thyristors during the commissioning process.
0 = No Trip; 1 = Trip.
Thermistor Trip (reserved)
Range: P51 / B5
Default: Off
Scaling: n/a
Type: R/W
Thermistor Selected – not available.
(P-73)
(P-74)
(P-75)
(P-76)
(P-77)
(P-72)
(P-126)
(P53.B5)
(P51.B5)
Chapter 5: Keypad Menu Items and Parameters
SR44 Series Soft Starter User Manual
1st Ed, Rev B 07/31/2019
Summary of Contents for Stellar SR44
Page 1: ...STELLAR SR44 SOFT STARTER USER MANUAL SR44 M WO 1st Edition Revision B...
Page 2: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 6: ...SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019 w 4 BLANK PAGE...
Page 8: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 12: ...Table of Contents BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019 t 4...
Page 23: ...ELECTRICAL INSTALLATION 2 CHAPTER CHAPTER 2 2 CHAPTER BLANK PAGE 2 1c...
Page 75: ...KEYPAD MENU ITEMS AND PARAMETERS CHAPTER 5 CHAPTER CHAPTER 5 BLANK PAGE 5 5 1c...
Page 237: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 238: ...SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...