1.8 – Clearance
To maintain adequate ventilation, each model of SR44 Soft Starter requires a minimum clearance
to adjacent equipment and partitions. These clearances are specified in the following diagram and
table.
S
T
B
F
Soft
Starter
Soft
Starter
Unit Air
Intake
Mounting
Surface
Outline of
Enclosure
S
Minimum Clearance for Heat Dissipation
SR44 Mounting Clearances
Model Number
Unit Cooling
Method
Minimum Clearance (mm [in])
Top (T)
Bottom (B)
Side (S)
Front (F)
SR44-9 to SR44-23
Natural Convection
75 [2.95]
75 [2.95]
15 [0.59]
25 [0.98]
SR44-30 to SR44-370
Forced Air with
internal cooling fan
inside each starter
Chapter 1: Mechanical Installation
SR44 Series Soft Starter User Manual
1st Ed, Rev B 07/31/2019