Chapter 5: Keypad Menu Items and Parameters
5.4.11 – ‘Parameters’ Menu (continued)
(reserved)
(reserved)
(reserved)
(reserved)
Bypass Upper Limit
Range: 1 to 50
Default: 12
Scaling: 1
Type: R/W
Bypass Upper Limit
• Associated with P121/B4, Op.
«•» This parameter bit is not fully functional in Bypass Operation unless a user-supplied external
current transformer is installed. (Refer to P18/B2, ‘Auto Bypass’.)
• Typically set about 80% of motor FLC.
• Current required = (motor FLC / SR44 FLC)*(32)
Bypass Lower Limit
Range: 0 to 150
Default: 10
Scaling: 1
Type: R/W
Bypass Lower Limit
• Associated with P121/B4, Op.
«•» This parameter bit is not fully functional in Bypass Operation unless a user-supplied external
current transformer is installed. (Refer to P18/B2, ‘Auto Bypass’.)
• Typically set about 40% of motor FLC.
• Current required = (motor FLC / SR44 FLC)*(32)
(reserved)
P-105
P-106
P-107
P-108
P-109
P-110
P-111
SR44 Series Soft Starter User Manual
1st Ed, Rev B 07/31/2019
5–72
Summary of Contents for Stellar SR44
Page 1: ...STELLAR SR44 SOFT STARTER USER MANUAL SR44 M WO 1st Edition Revision B...
Page 2: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 6: ...SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019 w 4 BLANK PAGE...
Page 8: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 12: ...Table of Contents BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019 t 4...
Page 23: ...ELECTRICAL INSTALLATION 2 CHAPTER CHAPTER 2 2 CHAPTER BLANK PAGE 2 1c...
Page 75: ...KEYPAD MENU ITEMS AND PARAMETERS CHAPTER 5 CHAPTER CHAPTER 5 BLANK PAGE 5 5 1c...
Page 237: ...BLANK PAGE SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...
Page 238: ...SR44 Series Soft Starter User Manual 1st Ed Rev B 07 31 2019...