Chapter 5: Keypad Menu Items and Parameters
5.4.4 – ‘Basic’ Menu (continued)
Protection
Range: 0 to 192
Default: 192
Scaling: n/a
Type: R/W
‘Protection Mode’ controls which trips are available:
• 64 = FULL = full protection with full volts after top of ramp; optimizing function turned off
• 192 = FULL+OPTIMIZE = full prot optimize
• 128 = START+BYPASS = protection during start; then bypass
• 0 = PHASE LOSS ONLY = I/p phase loss detection only
Start and Optimize mode is forced to ‘FULL’ Protection Mode when ‘Delta’ Firing Mode is selected
(P-6 = 1). In ‘PHASE LOSS ONLY’ Protection Mode (P-7 = 0), the bottom 12.5% of starter current
is ignored after TOR (Top Of Ramp).
(P-7)
SR44 Series Soft Starter User Manual
1st Ed, Rev B 07/31/2019
5–32