Remote
Stepping mode is active in the operation modes:
Remote
,
Remote II
,
Fieldbus
Local
Stepping mode is active in the operation modes:
Local
,
Service
Remote and local
Stepping mode is active in the operation modes:
Remote
,
Remote II
,
Fieldbus
,
Local
,
Service
Information
The timer cannot be by-passed in <Operation mode EMERGENCY>.
8.8.3.
Start and end of stepping mode
Start and end of stepping mode can be individually set for both directions.
Customer settings M0041
Timer M0142
End stepping CLOSE M0152
Start stepping CLOSE M0153
Start stepping OPEN M0154
End stepping OPEN M0155
Default values:
End stepping CLOSE
=
0.0 %
Start stepping CLOSE
=
100.0 %
Start stepping OPEN
=
0.0 %
End stepping OPEN
=
100.0 %
Setting ranges:
End stepping CLOSE
=
0.0 – 99.9 %
Start stepping CLOSE
=
0.1 – 100.0 %
Start stepping OPEN
=
0.0 – 99.9 %
End stepping OPEN
=
0.1 – 100.0 %
8.8.4.
On times and off times
On or off times can be set individually for directions OPEN and CLOSE.
Customer settings M0041
Timer M0142
On time CLOSE M0163
Off time CLOSE M0164
On time OPEN M0165
Off time OPEN M0166
Default values:
00:05.0 min : s
(= 5 seconds; for all on and off times)
Setting ranges:
00:01.0 ... 00:05.00.0 min : s
(= 1 second up to 30 minutes; for all
on and off times)
8.9.
Profibus DP interface
8.9.1.
Bus address (slave address)
The bus address can be entered manually via push buttons at the local controls
according to the description below. For information on how to set the bus address
via fieldbus, refer to Manual Device integration Profibus DP.
Customer settings M0041
Profibus DP M0016
DP1 slave address M0098
DP2 slave address M0295
Default value:
126
Setting range:
0 ... 126
Information
Parameter
DP2 slave address
is only available for some redundancy options.
74
Actuator controls
Application functions
ACV 01.2/ACVExC 01.2 Profibus DP