Figure 66:
Use push buttons
Up ▲ Down ▼
to select the desired parameter. The arrow below
the symbols shows the selected parameter. Pressing push button
Reset
resets the
lifetime account of the selected parameter to zero.
Set maintenance interval
Parameters for setting a defined maintenance interval. Once the set time has elapsed,
a maintenance signal is issued.
Required user level:
Specialist (4)
or higher.
Maintenance signals M1231
Maintenance M1644
Maintenance interval M1233
Default value:
10 years
Setting range:
1 month
...
10 years
15.6.
Operating times display
Characteristics
The actuator controls automatically determine the operating time for an operation
between two end positions. For both directions (from OPEN to CLOSE and from
CLOSE to OPEN), the last determined value is saved within a parameter.
Application
Operating time measurement indicated how an actuator installed in plant or a
combination of actuator/gearbox/valve behave with regard to inertia without performing
an operation and measuring the time manually.
Display measured operating times
Asset Management M1231
Operating time M1232
Operating time CLOSE M1234
Operating time OPEN M1235
Indications:
Operating time CLOSE
Indicates the measured operating time for the last operation in direction CLOSE
Operating time OPEN
Indicates the measured operating time for the last operation in direction OPEN
15.7.
Device temperature display
Required user level:
Specialist (4)
or higher.
Asset Management M1231
Device temperatures M0524
Indications:
Temp. controls
Indication of current temperature in actuator controls housing
Temp. control unit
Indication of current temperature in control unit of the actuator (actuator housing)
143
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP
Asset Management