Example: Activate pivot point 1 in operation direction OPEN
Customer settings M0041
Speed profile M2065
Pivot points OPEN M2067
Pivot point 1 OPEN M2125
Pivot point 1 OPEN M2076
Setting values:
Function active
<Speed profile> function is activated for the pivot point. When reaching the pivot
point, the actuator changes the speed to the value preset for this pivot point.
Function not active
<Speed profile> function is deactivated for the pivot point. The actuators passes the
pivot point without modifying the speed.
Define positions of pivot points
Each pivot point can be set to a value between 0 % and 100 % of the travel.
Information
The position of pivot points must be in ascending order (e.g. position 1 before position
2). If this is not the case, the actuator cannot be operated and actuators controls
generate a fault signal:
Config.fault speed prof.
Define pivot points for operation direction OPEN:
Customer settings M0041
Speed profile M2065
Pivot points OPEN M2067
Pivot point 1 OPEN M2125
...
Pivot point 9 OPEN M2133
Parameters for setting the positions (with default values):
Pivot 1 position OPEN M2096
=
10.0 %
Pivot 2 position OPEN M2097
=
20.0 %
Pivot 3 position OPEN M2098
=
30.0 %
Pivot 4 position OPEN M2099
=
40.0 %
Pivot 5 position OPEN M2100
=
50.0 %
Pivot 6 position OPEN M2101
=
60.0 %
Pivot 7 position OPEN M2102
=
70.0 %
Pivot 8 position OPEN M2103
=
80.0 %
Pivot 9 position OPEN M2104
=
90.0 %
Setting range:
0.0 ... 100.0 %
(in % before the end position, in relation to the full
travel)
Define pivot points for operation direction CLOSE:
Customer settings M0041
Speed profile M2065
Pivot points CLOSE M2066
Pivot point 1 CLOSE M2134
...
Pivot point 9 CLOSE M2142
Parameters for setting the positions (with default values):
Pivot 1 position CLOSE M2105
=
10.0 %
Pivot 2 position CLOSE M2106
=
20.0 %
Pivot 3 position CLOSE M2108
=
30.0 %
Pivot 4 position CLOSE M2109
=
40.0 %
Pivot 5 position CLOSE M2110
=
50.0 %
Pivot 6 position CLOSE M2111
=
60.0 %
Pivot 7 position CLOSE M2112
=
70.0 %
Pivot 8 position CLOSE M2113
=
80.0 %
55