5.
Signals (output signals)
5.1.
Signals via fieldbus
Feedback signals via fieldbus can be configured. Configuration is possible for both
data structure and data contents.
Configuration is defined via the GSD file only.
Information
If required, download the GSD file (General Station Description) from the Internet:
www.auma.com
For information on the feedback signals via fieldbus and the configuration of the
parameters via fieldbus interface, refer to Manual (Device integration fieldbus) Profibus
DP.
5.2.
Status signals via output contacts (digital outputs)
Conditions
Output contacts are only available if a parallel interface is provided in addition to the
fieldbus interface.
Characteristics
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
5.2.1.
Assignment of outputs
The output contacts (outputs DOUT 1 – 6) can be assigned to various signals.
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Default values:
Signal DOUT 1
=
Fault
Signal DOUT 2
=
End position CLOSED
Signal DOUT 3
=
End position OPEN
Signal DOUT 4
=
Selector sw. REMOTE
Signal DOUT 5
=
Torque fault CLOSE
Signal DOUT 6
=
Torque fault OPEN
Further setting values:
Refer to <Appendix>/<Selection overview for output contacts and indication lights>
5.2.2.
Coding the outputs
The output signals
Coding DOUT 1
–
Coding DOUT 6
can be set either to high active
or low active.
●
High active = output contact closed = signal active
●
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1
=
Low active