●
Status indications:
S0005
or
S0008
-
Details:
Wrn op.mode starts
●
Status indications:
S0005
or
S0008
-
Details:
Wrn op.mode run time
The warning signals will automatically be cleared if the permissible motor starts per
second or the permissible running time per hour are no longer reached.
The operational info logger records the number of excesses (warnings) as well as
the number of motor starts and motor running times.
Asset Management M01231
Operational info M0177
Operational info M0188
On time warning 1 M0325
contains total number of all on time warnings.
On time warning 2 M0326
contains maximum duration of on time warning
Example:
Due to excess of defined starts/h or defined running time/h, AC issue in total 4 on
time warnings: two for 5 min, once for 10 min, once for 17 min. Afterwards the
operating data counters contain the following values:
On time warning 1 M0325
= 37 min = total of all periods (5+5+10+17 min)
On time warning 2 M0326
= 17 min = longest period
Figure 49: Example
[1]
Running time/h
[2]
Starts/h
[3]
On time warning
Activate on time monitoring
Required user level:
Specialist (4)
or higher.
Customer settings M0041
Duty type monitoring M0355
Duty type monitoring M0358
Default value:
Function not active
Setting values:
Function not active
Function <On-time monitoring> deactivated.
Function active
Function <On-time monitoring> activated.
Set permissible starts/h
Customer settings M0041
Duty type monitoring M0355
Permissible starts M0357
Default value:
1,200
starts/h
Setting range:
1 ... 1,800
starts/h
Set permissible running time/h
Customer settings M0041
Duty type monitoring M0355
Perm. run time M0356
108
Actuator controls
Monitoring functions
ACV 01.2/ACVExC 01.2 Profibus DP