Set max. value, scaling and unit
Required user level:
Specialist (4)
or higher.
Display M0009
Units M1205
Process factor M1211
Max. value at 100.0 % M1213
Scaling M1214
Unit M1215
Default values:
Max. value at 100.0 %
=
1000
Scaling
=
1
Unit
=
mA
Setting ranges/values:
Max. value at 100.0 %
=
1 – 1000
Scaling
=
0.001 – 1000
(multiplier factor for unit)
Unit
=
mA; °C; bar; m³/h; m³/min; m; cm; mm; °
7.5.8.
Analogue working value units (AIN)
Activate working value units (AIN)
Required user level:
Specialist (4)
or higher.
Display M0009
Units M1205
Working values (AIN) M1216
Work. val. activ. (AIN) M1217
Default value:
Function not active
Setting values:
Function not active
<Working value units (AIN)> function deactivated.
Function active
<Working value units (AIN)> function activated.
Set max. value, scaling and unit
Required user level:
Specialist (4)
or higher.
Display M0009
Units M1205
Working values (AIN) M1216
Max. value at 100.0 % M1217
Scaling M1218
Unit M1219
Default values:
Max. value at 100.0 %
=
1000
Scaling
=
1
Unit
=
mA
Setting ranges/values:
Max. value at 100.0 %
=
1 – 1000
Scaling
=
0.001 – 1000
(multiplier factor for unit)
Unit
=
mA; °C; bar; m³/h; m³/min; m; cm; mm; °
7.5.9.
Analogue signal output units (AOUT)
Activate signal output units (AOUT)
Required user level:
Specialist (4)
or higher.
Display M0009
47
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP
Basic settings for commissioning