8.4.1.
Operation profile: activate
Required user level:
Specialist (4)
or higher.
Device configuration M0053
Application functions M0178
Activation M0212
Operation profile M0294
Default value:
Function not active
Setting values:
Function not active
Function <Operation profile> deactivated.
Function active
Function <Operation profile> activated.
8.4.2.
Operation profile for intermediate positions (pivot points): set
When reaching an intermediate position, the operation behaviour of the actuator
may be set.
Customer settings M0041
Intermediate positions M0143
Operation behaviour M0257
Operation behaviour 1 M0258
Default value:
Off
Setting values:
Off
No intermediate stop, actuator continues the operation.
Stop in OPEN
●
Actuator stops at pivot point during operation in direction OPEN.
●
The operation command has to be cleared by means of the STOP command
and a new operation command has to be sent to resume operation.
●
This function is not active in operation mode Remote SETPOINT.
Stop in CLOSED
●
Actuator stops at pivot point during operation in direction CLOSE.
●
The operation command has to be cleared by means of the STOP command
and a new operation command has to be sent to resume operation.
●
This function is not active in operation mode Remote SETPOINT.
Stop in OPEN & CL.
●
Actuator stops automatically upon reaching the pivot point.
●
The operation command has to be cleared by means of the STOP command
and a new operation command has to be sent to resume operation.
●
This function is not active in operation mode Remote SETPOINT.
Off time in OPEN
Actuator stops at pivot point during operation in direction OPEN. If an operation
command in direction OPEN is present at the end of the pause time, the actuator
resumes operation into direction OPEN. If an operation command in direction CLOSE
is present during the pause time, the pause is aborted and operation into direction
CLOSE resumed.
Off time in CLOSED
When reaching the pivot point, the actuator stops during operation in direction CLOSE.
If an operation command in direction CLOSE is present at the end of the pause time,
the actuator resumes operation into direction CLOSE. If an operation command in
direction OPEN is present during the pause time, the pause is interrupted and
operation into direction OPEN resumed.
Off time in OPEN & CL.
Actuator stops automatically upon reaching the pivot point. If an operation command
in direction OPEN or CLOSE is present at the end of the pause time, the actuator
resumes operation depending on the operation command.
Information
The actuator stops for each activated intermediate position for which operation be-
haviour
Stop in OPEN
,
Stop in CLOSED
or
Stop in OPEN & CL.
is assigned.
59
Actuator controls
ACV 01.2/ACVExC 01.2 Profibus DP
Application functions