Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: press and enter ID
M0084
.
➥
Display indicates:
Set end pos.CLOSED?
CLOSED or OPEN
4.
Select via
Up ▲ Down ▼
:
→
▶ Set end pos.CLOSED? M0084
→
▶ Set end pos. OPEN? M0085
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
The display indicates either:
-
Set end pos.CLOSED? CMD0009 →
continue with step 9
-
Set end pos. OPEN? CMD0010 →
continue with step 12
-
Specialist (4) →
continue with step 6
User login
6.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher
➥
The symbols have the following meaning:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
7.
Press
Ok
to confirm selected user.
➥
Display indicates:
Password 0***
8.
Enter password (
→
enter password).
➥
The display indicates either:
-
Set end pos.CLOSED? CMD0009 →
continue with step 9
-
Set end pos. OPEN? CMD0010 →
continue with step 12
Set end position
CLOSED
CMD0009
9.
Set end position CLOSED again :
9.1 For large strokes: Set selector switch in position Local control (LOCAL)
and operate actuator in motor operation via push button
(CLOSE) in
direction of the end position.
Information: Stop actuator before reaching end of travel (press STOP
push button to avoid damage.
9.2 Engage manual operation.
9.3 Turn handwheel until valve is closed.
9.4 Turn back the handwheel by an amount equal to the overrun.
9.5 Set selector switch to position 0 (OFF).
➥
Display indicates:
Set end pos.CLOSED? Yes No
40
Actuator controls
Basic settings for commissioning
ACV 01.2/ACVExC 01.2 Profibus DP