59A
Speed min. voltage for winter auto fan
Speed max. voltage for winter auto fan
Speed min. voltage for summer auto fan
Speed max. voltage for summer auto fan
Cooling proportional band
Heating proportional band
General reset and restore of default values
Confirmation with O/I and Fan buttons
THERMOSTAT PARAMETERS
THERMOSTAT PARAMETERS
OFS
I-rL
Thermostat NTC probe offset variation
Relay hysteresis
± 3°C
0°C
dS
Set variation range with T–MB
± 9°C
± 3°C
0,5 ÷ 2,0°C
0,7°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
PARAMETERS of the T2 probe, CHANGE-OVER
T2-1
T2-2
Status changeover from ventilation to cooling
Status changeover from ventilation to heating
15 ÷ 24°C
<=20°C
30 ÷ 36°C
>=32°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
PARAMETERS of the T3 probe, TME minimum probe
T3-1
T3-2
Fan ON in heating mode (T3 probe)
Fan ON in cooling mode (T3 probe)
30 ÷ 40°C
>=34°C
10 ÷ 25°C
<=22°C
I-T3
T3 probe hysteresis
2 ÷ 8°C
5°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
OTHER FUNCTIONS
rE-t
F
UNCTION
D
ESCRIPTION
O
PERATION
PARAMETERS of the Stratification Cycle
t1SE
t1SI
Decompensation air probe T1 in cooling mode
Decompensation air probe T1 in heating mode
0,5 ÷ 2,0°C
0,7°C
0,5 ÷ 2,0°C
1,2°C
Ft1
Fan OFF time
10 - 20 min.
15 min.
Ft2E
Ft2I
Stratification time in cooling mode
30 - 180 sec.
120 sec.
Stratification time in heating mode
30 - 180 sec.
150 sec.
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
THERMOSTAT PARAMETERS
SHu3
SCu2
Speed max. voltage
Speed medium voltage
6 ÷ 10 V
10 V
3 ÷ 8 V
5 V
Slu1
Speed min. voltage
1 ÷ 6 V
1 V
LLSI
1 ÷ 6 V
1 V
HLSI
5 ÷ 10 V
10 V
LLSE
1 ÷ 6 V
1 V
HLSE
5 ÷ 10 V
10 V
PFC
2,0 ÷ 6,0°C
3,5°C
PFH
2,0 ÷ 6,0°C
3,5°C
F
UNCTION
D
ESCRIPTION
R
ANGE
D
EFAULT
> 3 sec.
FEATURES FOR FACTORY
This menu allows modifying the operation
parameters of the thermostat, electronic motor, of the +/- 3 version
and many other parameters (pump cycle, RESET).
With the control set on
“OFF”
, press
the
M
and
Fan
buttons simultaneously for 3 seconds.
Select the desired parameter to be modified,
pressing button “+” or “-” and confirm using the “M” button.
Once the parameter is selected, the value will be displayed.
The value can be modified using button “+” or “-”.
Press the “M” button once to turn back to the parameter selection;
to exit the menu, press the “M” button for more than 5 seconds.