Electrical installation
GasEye Cross Duct
Operating instructions, 05/2021
61
RTD
GasEye system provides the resistance temperature detectors (RTDs) input for
measuring the process temperature. The system can be configured with two dip
switches to operate with PT100/PT1000 and 2-,3-,4-wire connection. Please refer
Figure 60 to Figure 62 for signal connection.
Figure 60. Exemplary usage of 2-wire RTD.
WARNING
RTD
2-wire RTD require additional terminal connection, please make the external
jumper for 11 and 12 as well for 36 and 35.