Electrical installation
GasEye Cross Duct
Operating instructions, 05/2021
117
ALARM10.SIGNAL
0xEE
238 Alarm signal selection
ALARM10.OPERATOR
0xEF
239 Alarm mathematical operator
ALARM10.THRESHOLD
0xF0
240 16 -bits of floating point value (first
part)
Alarm threshold value
0xF1
241 16 -bits of floating point value
(second part)
Alarm threshold value
ALARM10.HYSTERESIS
0xF2
242 16 -bits of floating point value (first
part)
Alarm hysteresis value
0xF3
243 16 -bits of floating point value
(second part)
Alarm hysteresis value
HMI.PASSWORD
0xF4
244 HMI pin need to change
parameters from HMI panel (value
range 0-9999)
Modbus TCP
Modbus TCP is an Anybus CompactCom module integrated with Analyzer.
Communication parameters are configured by Analyzer web server tool (only TCP
PORT number is static).
TCP port number: 502
Modbus register map is common for RTU/TCP and is describe in previous chapter.
Profinet
Profinet is Anybus CompactCom module integrated with Analyzer. Communication
parameters are configured by Analyzer web server tool.
Data transmitted by protocol are describe in Modbus RTU chapter and can be find in
GSDML configuration file deliver with device.
Add-on module
Mechanical connection of the ABCC-M40 module to the PCB board GasEye Host ver.
4.X.
Elements of the ABCC-M40 module: