Electrical installation
82
GasEye Cross Duct SG and MG
Operating instructions, 05/2021
Table 7. Modbus Input register map (function 0x4).
Register Name
Register
address
(hex)
Register
address
(dec)
Comments
PROCESS.TEMPERATURE
0x00
0
16 -bits of floating point value (first
part)
Process tempetature
0x01
1
16 -bits of floating point value
(second part)
Process tempetature
PROCESS.PRESSURE
0x02
2
16 -bits of floating point value (first
part)
Process pressure
0x03
3
16 -bits of floating point value
(second part)
Process pressure
TEMP.CALCULATED
0x04
4
16 -bits of floating point value (first
part)
Temperature calculate available
only in specific configuration
0x05
5
16 -bits of floating point value
(second part)
Temperature calculate available
only in specific configuration
GAS101.CONCENTRATION
0x06
6
16 -bits of floating point value (first
part)
Gas concentration
0x07
7
16 -bits of floating point value
(second part)
Gas concentration
GAS102.CONCENTRATION
0x08
8
16 -bits of floating point value (first
part)
Gas concentration
0x09
9
16 -bits of floating point value
(second part)
Gas concentration
GAS103.CONCENTRATION
0x0A
10
16 -bits of floating point value (first
part)
Gas concentration
0x0B
11
16 -bits of floating point value
(second part)
Gas concentration
GAS104.CONCENTRATION
0x0C
12
16 -bits of floating point value (first
part)
Gas concentration