Monitoring of DC analog measurements
&KDSWHU
0RQLWRULQJ
If a 0.1 mA variation in the monitored quantity for 10 minutes (600 s) is the event that
should cause the trigger of the IDBS monitoring (reporting of the value because of
IDBS threshold operation) and the sampling frequency (SampRate) of the monitored
quantity is 5 Hz, than the set value for IDBS (IDeadB) will be 300 mA:
(Equation 81)
(Equation 82)
The polarity of connected direct current input signal can be changed by setting the
ChSign to On or Off. This way it is possible to compensate by setting the possible
wrong connection of the direct current leads between the measuring converter and the
input terminals of the REx 5xx series unit.
The setting table lists all setting parameters with additional explanation.
where:
IDeadB
is the set value of the current level for IDBS in mA.
SampRate
is the sampling rate (frequency) set value, in Hz.
ts = 1/SampRate
is the time between two samples in s.
IDBS
0.1 600
⋅
60 mA s
]
[
=
=
IDeadB
IDBS SampRate
⋅
60 5
⋅
300 mA
]
[
=
=
=
1RWH
,WLVLPSRUWDQWWRVHWWKHWLPHIRUSHULRGLFUHSRUWLQJDQGGHDGEDQGLQDQRSWLPL]HGZD\
WRPLQLPL]HWKHORDGRQWKHVWDWLRQEXV
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...