Apparatus control
&KDSWHU
&RQWURO
SWICONB: Used for external synchro-check function and individual phase position in-
dication. Normally used for circuit breakers.
SWICONC: Used for common position indication for all three phases. Normally used
for disconnectors and earthing switches.
The BLKCON element consists of two variants:
BLKCONK: Normally used for the bays.
BLKCONL: Normally used for the apparatuses.
With control functions applicable for one bay, these standard modules are available:
$OWHUQDWLYHIRURQHED\DQGXSWRDSSDUWXVHV
Normal use:
•
1 pcs BAYCONA
with external selection relays with individual feedback signals:
•
1 pcs BAYCONE
and either
•
2 pcs SWICONA (internal synchro-check) or
•
2 pcs SWICONB (external synchro-check)
and
•
8 pcs SWICONC and
•
8 pcs COMCON and
•
8 pcs BLKCONL and
•
1 pcs BLKCONK
$OWHUQDWLYHIRURQHED\DQGXSWRDSSDUDWXVHV
Normal use:
•
1 pcs BAYCONA or
•
2 pcs BAYCONB or