394
Serial communiction, IEC
&KDSWHU
'DWDFRPPXQLFDWLRQ
6HULDOFRPPXQLFWLRQ,(&
$SSOLFDWLRQ
The IEC 60870-5-103 communication protocol is mainly used when a protection termi-
nal communicates with a third party control or monitoring system. This system must
have a software that can interpret the IEC 60870-5-103 communication messages.
)XQFWLRQDOLW\
The IEC 60870-5-103 is an unbalanced (master-slave) protocol for coded-bit serial
communication exchanging information with a control system. In IEC terminology a
primary station is a master and a secondary station is a slave. The communication is
based on a point to point principle. The master must have a software that can interpret
the IEC 60870-5-103 communication messages. For detailed information about IEC
60870-5-103, refer to the IEC60870 standard part 5: Transmission protocols, and to the
section 103: Companion standard for the informative interface of protection equipment.
'HVLJQ
*HQHUDO
The protocol implementation in REx 5xx consists of the following functions:
•
Event handling
•
Report of analog service values (measurands)
•
Fault location
•
Command handling
-
Autorecloser ON/OFF
-
Teleprotection ON/OFF
-
Protection ON/OFF
-
LED reset
-
Characteristics 1 - 4 (Setting groups)
•
File transfer (disturbance files)
•
Time synchronization
+DUGZDUH
When communicating locally with a Personal Computer (PC) or a Remote Terminal
Unit (RTU) in the station, using the SPA/IEC port, the only hardware needed is:
•
Optical fibres, glass/plastic
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...