201
Apparatus control
&KDSWHU
&RQWURO
$XWRPDWLFRSHUDWLRQFKHFN
BAYCON has an amount of information that concerns the permission for automatic op-
eration. This information is made available at the AU_OP_Vx outputs. Other elements
can combine this information to a signal to an automatic function indicating permission
for operation.
3DUDPHWHUV
7B&$1B5(
Time-out when the reset of the reservation acknowledgement is not done by the request-
ing bays, for example, because of communication error.
&20&21
)XQFWLRQDOLW\
COMCON acts as an interface between the possible operator places and the bay and the
apparatus-control program. The validity of operator places is indicated on the RE-
MOTE, STATION and LOCAL inputs. Only the signals from the operator place(s) that
are valid are executed. When a change occurs, COMCON checks validity and forwards
the commands to the outputs, if they are correct.
From station level, COMCON supports two ways of command executions:
1. From station HMI.
2. From remote gateway.
In the first way, that is normally used as standard from the station HMI (see item 1 in
figure 87), only one selection input is activated, S_SEL_O or S_SEL_C. COMCON
sets the RQ_SEL and the concerning direction output, OPEN or CLOSE. After the SE-
LECT input is set by BAYCON, it allows the execute command S_OPEN and
S_CLOSE to pass through. These execution inputs can be set at the same time or before
SELECT is activated. Then the EXECUTE output is also activated.
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...