
61
3 zone impedance protection (Z(n)RW)
&KDSWHU
/LQHLPSHGDQFH
Conventional earth return compensation is used for phase to earth fault in two phase sol-
idly earthed systems (example for a phase L1 to earh fault):
(Equation 16)
where
(Equation 17)
and I
N
is a phasor of the residual current in the relay point.
The calculation of apparent impedances for phase-to-phase faults follows the equation:
(Equation 18)
U and I is the corresponding voltage and current phasors in the respective phase.
The use of zero sequence compensator factor (K
N
) results in the same reach along the
line for all types of faults.
The apparent impedance is considered as an impedance loop with resistance R and re-
actance X, as presented in figure 32.
Z
ap
U
L1
I
L1
K
N
I
N
⋅
+
------------------------------
=
K
N
1
2
---
Z
0
Z
1
–
Z
1
--------------------
⋅
=
Z
ap
U
L1
U
L2
–
I
L1
I
L2
–
-------------------------
=
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...