Automatic switch onto fault logic (SOTF)
&KDSWHU
/LQHLPSHGDQFH
The external activation is achieved by an input (SOTF-BC), which should be set high
for activation, and low when the breaker has closed. This is carried out by an NC aux-
iliary contact of the circuit breaker or by the closing order to the breaker.
The internal automatic activation is controlled by the DLD function and its functional
output DLD--START. The DLD--START functional output is activated when all phase
voltages and phase currents have been below their set operate values. The DLD--
START functional output is usually configured to the SOTF-DLCND functional input.
It activates the operation of the SOTF function, if present for more than 200 ms without
the presence of a non-directional impedance starting signal SOTF-NDACC.
Operation of a SOTF function can be blocked by the activation of a SOTF-BLOCK
functional input.
&DOFXODWLRQV
6HWWLQJLQVWUXFWLRQV
The parameters for the switch-onto-fault function are set via the local HMI or PST (Pa-
rameter Setting Tool). Refer to the Technical reference manual for setting parameters
and path in local HMI.
The low voltage and low current criteria for automatic activation is settable under the
DLD-- function. Refer to the Technical reference manual for setting parameters and
path in local HMI.
This setting is not critical as long as it is lower then the lowest operation voltage during
normal and emergency conditions.
The distance protection zone used for a switch-onto-fault criterion (SOTF zone) have
to be set to cover the entire protected line with a safety margin of minimum 20%.
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...