Automatic reclosing function (AR)
&KDSWHU
&RQWURO
There is an AR State Control, see Function block diagrams, to track the actual state in
the reclosing sequence.
3XOVLQJRI&%FORVLQJFRPPDQG
The circuit breaker closing command, AR01-CLOSECB, is made as a pulse with a du-
ration, set by the tPulse parameter. For circuit breakers without an anti-pumping func-
tion, the closing-pulse-cutting described below can be used. It is selected by means of
the CutPulse parameter (set to On). In case of a new trip pulse, the closing pulse will be
cut (interrupted). But the minimum length of the closing pulse is always 50 ms.
At the issue of a reclosing command, the associated reclosing operation counter is also
incremented. There is a counter for each type of reclosing and one for the total number
of reclosings. See Function block diagrams.
7UDQVLHQWIDXOW
After the reclosing command, the reclaim timer keeps running for the set time. If no
tripping occurs within this time, tReclaim, the auto-reclosing function will be reset. The
circuit breaker remains closed and the operating gear ready (manoeuvre spring is re-
charged). AR01-CBCLOSED = 1 and AR01-CBREADY = 1.
After the reclaim time, the AR state control resets to original rest state, with AR01-SE-
TON = 1, AR01-READY = 1. The other AR01 outputs = 0.
8QVXFFHVVIXOVLJQDO
Normally the signal AR01-UNSUC appears when a new start is received after the last
reclosing attempt has been made. See Function block diagrams. It can be programmed
to appear at any stage of a reclosing sequence by setting the parameter
8QVXF0RGH
=
On. The UNSUC signal is attained after the time tUnsuc.
3HUPDQHQWIDXOW
If a new trip takes place after a reclosing attempt and a new AR01-START or AR01-
TRSOTF signal appears, the AR01-UNSUC (Reclosing unsuccessful) is activated. The
timer for the first reclosing attempt (t1) cannot be started.
Depending on the PulseCut parameter setting, the closing command may be shortened
at the second trip command.
After time-out of the reclaim timer, the auto reclosing function resets, but the circuit
breaker remains open (AR01-CBCLOSED = 0, AR01-CBREADY = 1). Thus the re-
closing function is not ready for a new reclosing cycle. See Function block diagrams
and Sequence examples.
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...