281
Interlocking
&KDSWHU
&RQWURO
)LJXUH6ZLWFK\DUGOD\RXWEUHDNHUDQGDKDOI
&RQILJXUDWLRQ
For a breaker-and-a-half arrangement, the modules BH_LINE_A, BH_CONN and
BH_LINE_B must be used.
3DUDPHWHUVHWWLQJ
For application without Q9 and Q8, just set the appropriate inputs to open state and dis-
regard the outputs. In the functional block diagram, 0 and 1 are designated 0=FIXD-
OFF and 1=FIXD-ON:
•
Q9_OP = 1
•
Q9_CL = 0
•
Q8_OP = 1
•
Q8_CL = 0
If, in this case, a line voltage supervision is added, then rather than setting Q9 to open
state, specify the state of the voltage supervision:
•
Q9_OP = VOLT_OP
99000360.vsd
Q1
Q51
Q52
Q0
Q6
Q9
Q8
Q2
Q51
Q52
Q0
Q6
Q53
Q53
Q61
Q62
Q0
Q9
Q8
Q51
Q52
BH_CONN
BH_LINE_B
BH_LINE_A
A (BB1)
B (BB2)