352
Monitoring of AC analog measurements
&KDSWHU
0RQLWRULQJ
The dead-band limits can be set directly in the corresponding units of the observed
quantity for the:
•
Amplitude dead-band supervision (ADBS)
•
Integrating dead-band supervision (IDBS)
The IDBS area is defined by the following formula:
(Equation 77)
Where:
The setting value for IDBS is IDeadB, and is expressed in the measuring unit of the
monitored quantity (kV, A, MW, Mvar, MVA or Hz). The value is reported if the time
integral area is greater than the value IDBS.
If a 0.1 Hz variation in the frequency for 10 minutes (600 s) is the event that should
cause the reporting of the frequency monitored value, than the set value for IDeadB is
60 Hz.
The hysteresis can be set under the setting Hysteres.
Alarm and warning thresholds have to be set respectively under the settings HiAlarm
(LowAlarm) and HiWarn (LowWarn).
IDeadB
is a set operating value for IDBS in corresponding unit.
ReadFreq
is the reading frequency. It has a constant value of 1Hz.
ts = 1/ReadFreq
is the time between two samples (fixed to 1s).
IDBS
IDeadB
ReadFreq
-----------------------------
IDe adB ts
⋅
=
=
1RWH
,WLVLPSRUWDQWWRVHWWKHWLPHIRUSHULRGLFUHSRUWLQJDQGGHDGEDQGLQDQRSWLPL]HGZD\
WRPLQLPL]HWKHORDGRQWKHVWDWLRQEXV
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...