158
Fuse failure supervision (FFRW)
&KDSWHU
6HFRQGDU\V\VWHPVXSHUYLVLRQ
)XVHIDLOXUHVXSHUYLVLRQ))5:
$SSOLFDWLRQ
Different protection functions within the REO 517 protection, control and monitoring
terminals operate on the basis of the measured voltage in the relay point. Examples are:
distance protection function, undervoltage measuring function and voltage check for
the weak infeed logic.
These functions can operate unnecessarily if a fault occurs in the secondary circuits be-
tween the voltage instrument transformers and the terminal.
It is possible to use different measures to prevent such unwanted operations. Miniature
circuit breakers in the voltage measuring circuits, located as close as possible to the
voltage instrument transformers, are one of them. Separate fuse-failure monitoring re-
lays or elements within the protection and monitoring devices are another possibilities.
These solutions are combined to get the best possible effect in the fuse failure supervi-
sion function of REx 5xx terminals.
The fuse-failure supervision function, FFRW is intended for single- and two-phase sys-
tems.
The fuse-failure supervision function integrated in the REO 517 works as follows:
•
On the basis of external binary signals from the miniature circuit breaker or from
the line disconnector. In the first case all voltage dependent functions are affected.
However, in the second case the impedance measuring function is not affected.
•
based on changes: a large change in the voltage without a corresponding large
change in the current.
)XQFWLRQDOLW\
The current and voltage measuring elements within one of the built-in digital signal pro-
cessors continuously measure the currents and voltages in all phases and calculate:
•
The change of current
∆
I/
∆
t
•
The change of voltage
∆
U/
∆
t
comparing them with their respective set values
∆
I< and
∆
U>.
The function becomes active one and a half period after the voltage exceeds the set op-
erate value U<.
Summary of Contents for REO 517
Page 10: ... RQWHQWV ...
Page 16: ...6 Introduction to the application manual KDSWHU QWURGXFWLRQ ...
Page 64: ...54 Blocking of signals during test KDSWHU RPPRQ IXQFWLRQV ...
Page 88: ...78 Scheme communication logic ZCOM KDSWHU LQH LPSHGDQFH ...
Page 146: ...136 Unbalance protection for capacitor banks TOCC KDSWHU XUUHQW ...
Page 166: ...156 Dead line detection DLD KDSWHU 3RZHU V VWHP VXSHUYLVLRQ ...
Page 378: ...368 Monitoring of DC analog measurements KDSWHU 0RQLWRULQJ ...
Page 384: ...374 Pulse counter logic PC KDSWHU 0HWHULQJ ...
Page 412: ...402 Serial communication modules SCM KDSWHU DWD FRPPXQLFDWLRQ ...
Page 440: ...430 LED indication module KDSWHU DUGZDUH PRGXOHV ...