IEC140000137-1-en.vsd
IEC140000137 V1 EN
3.3. Set the
Host IP
as the PMU IP address configured for the port in use. Here the
LANAB:1 IPAddress (192.168.1.10) is set.
3.4. Set the
Port
as the TCP port defined in the PMU for control of data sent over
UDP client group 1 (Default value: 4713). This can be found under the
parameter
TCPportUDPdataCtrl1
as one of the UDP communication
parameters.
3.5.
Save
the
Alternate Command Channel Configuration
settings.
Verifying the IEEE C37.118/1344 UDP
9.5
Verifying the communication
Connect your PC to the substation network and ping the connected IED and the Substation
Master PC, to verify that the communication is working (up to the transport layer). Make
sure that the optical fibers are connected correctly.
After checking the communication, it is time to verify the IEEE C37.118/1344
communication over both TCP and UDP protocols.
One way to verify the communication up to the application layer is to use a protocol
analyzer connected to the substation bus, and monitor the communication. Alternatively,
the PMU Connection Tester tool can be used to verify the IEEE C37.118/1344
communication. The section
Setting the TCP/UDP client communication
Section 9
1MRK 504 165-UUS -
Establishing connection and verifying the IEEE C37.118/1344 communication
78
Transformer protection RET670 2.2 ANSI
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...