Checking the case without re-trip,
RetripMode = Retrip Off
1.
Set
RetripMode
=
Retrip Off
.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the
set current value.
3.
Verify that no re-trip, but back-up trip is achieved after set time.
4.
Disconnect AC and BFI_3P input signals.
Checking the re-trip with current check,
RetripMode = CB Pos Check
1.
Set
RetripMode
=
CB Pos Check
.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the
set current value.
3.
Verify that re-trip is achieved after set time
t1
and back-up trip after time
t2
.
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with current
below set current value.
5.
Verify that no re-trip and no back-up trip are obtained.
6.
Disconnect AC and BFI_3P input signals.
Checking re-trip without current check
1.
Set
RetripMode
=
No CBPos Check
.
2.
Apply the fault condition, including initiation of CCRBRF (50BF), well above the
set current value.
3.
Verify that re-trip is achieved after the set time
t1
, and the back-up trip after time
t2
.
4.
Apply the fault condition, including initiation of CCRBRF (50BF), with current
below set current value.
5.
Verify that re-trip is achieved after set time
t1
, but no back-up trip is obtained.
6.
Disconnect AC and BFI_3P input signals.
11.5.8.5
Verifying the back-up trip mode
In the cases below it is assumed that
FunctionMode
=
Current
is selected.
Checking that back-up tripping is not achieved at normal CB tripping
Use the actual tripping modes. The case below applies to re-trip with current check.
1.
Apply the fault condition, including initiation of CCRBRF (50BF), with phase
current well above set value
Pickup_PH
.
2.
Interrupt the current, with a margin before back-up trip time,
t2
. It may be made at
issue of re-trip command.
3.
Check that re-trip is achieved, if selected, but no back-up trip is obtained.
4.
Disconnect AC and BFI_3P input signals.
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
193
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...