binary output for a low pulse command in the Signal Matrix in PCM600 and
monitoring a positive from this output.
6.
Return the applied voltage to
VSet
.
11.10.3.4
Check the undervoltage block function
1.
Confirm the setting for
Vblock
, nominally at 80% of rated voltage.
2.
Confirm the voltage control function response to an applied voltage below
Vblock
,
by reviewing the setting in the local HMI under
Main menu/Settings/General
settings/Control/TransformerVoltageControl(ATCC,90)/TR1ATCC:x/
TR8ATCC:x/UVBk
that may cause an alarm, total or automatic block of the
voltage control function to be displayed on the local HMI.
3.
Apply a voltage slightly below
Vblock
and confirm the response of the voltage
control function.
11.10.3.5
Check the upper and lower busbar voltage limit
1.
Confirm the settings for
Vmin
and
Vmax
in the local HMI under
Main menu/
Settings/Setting group N/Control/TransformerVoltageControl(ATCC,90)/
TR1ATCC:x/TR8ATCC:x/Voltage/Umax or Umin
and
Main menu/
Settings/IED Settings/Control/TR8ATCC (90)/TR8ATCC:n/Voltage/Umax
2.
Confirm the voltage control function response to an applied voltage below
Vmin
and
above
Vmax
, by reviewing the settings in the local HMI under
Main menu/Settings/
General settings/Control/TransformerVoltageControl(ATCC,90)/
TR1ATCC:x/TR8ATCC:x/UVPartBk
and
Main menu/General Settings/
Control/TransformerVoltageControl/TR1ATCC:x/TR8ATCC:x/OVPartBk
.
These conditions may cause an alarm or total block of the voltage control function
to be displayed on the local HMI.
3.
Decrease the injected voltage slightly below the
Vmin
value and check for the
corresponding blocking or alarm condition on the local HMI. For an alarm
condition, the voltage regulation function is not blocked and a raise command
should be issued from the IED.
4.
Increase the applied voltage slightly above the
Vmax
value and check for the
corresponding blocking or alarm condition on the local HMI. For an alarm
condition, the voltage regulation function is not blocked and a lower command
should be issued from the IED.
11.10.3.6
Check the overcurrent block function
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
251
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...