Test point
Reach
Value
Comments
3
X
0.8 x (2 x X1
set
+ X0
set
)/3
R
0.8 x (2 x R1
set
+ R0
set
)/3 +RFPG
set
4
X
0.5 x (2 x X1
set
+ R0
set
)/3
R
0.5 x (2 x R1
set
+R0
set
)/3 + RFPG
set
5
X
0.85 x RFPG
set
x tan(LdAngleset)
LdAngle = angle for the maximal load
transfer.
R
0.85 x RFPG
6
X
RLdFwdset x tan(LdAngleSet)
R
RLdFwd
set
7
X
0
R
RLdFwd
set
8
X
–02143 x RLdFwd
set
Exact: 0.8 x RFPG x tan (ArgDir)
R
0.8 x RLdFwd
set
9
X
–0.8 x RLdFwd
set
x tan(ArgDir)
R
0.8 x RLdFwd
set
10
X
0.17 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2 x X1
set
X0
set
)/3
R
-0.36 x (2 x X1
set
+ X0
set
)
Exact: 0.5 x (2X1
set
+ X0
set
)/(3 x
tan(AgNegDir90)
11
X
0.27 x (2 x X1
set
+X0
set
)
Exact: 0.8 x (2 x X1
set
+ X0
set
)/3
R
–0.57 x (2 x X1
set
+ X0
set
)
Exact: 0.8 x ( X0set)/(3 x
tan(AngNegDir 90))
12
X
0.5 x (2 x X1
set
+ X0
set
)/3
R
0.5 x (2 x R1
set
+ R0
set
)/3
13
X
0
R
RFPG
11.4.5.1
Measuring the operating limit of set values
Procedure:
1.
Subject the IED to healthy normal load conditions for at least two seconds.
2.
Apply the fault condition and slowly decrease the measured impedance to find the
operating value of the phase-to-phase fault for zone 1 according to test point 1 in
figure
and table
. Compare the result of the measurement with the set value.
3.
to find the operating value for test points 2, 3 in table
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
127
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...