transformer can be observed as service values on the local HMI and raise/lower
commands detected from the binary output mapped in the Signal Matrix.
The voltage injection equal to
VSet
is required for both transformers
during this test.
12. Confirm that a tap change command is issued from the voltage control function to
compensate for the circulating current.
13. Injected currents can be reversed such that the direction of calculated circulating
currents change polarity, which will cause a lower command for Transformer 2 and
a raise command for Transformer 1.
Circulating current limit
1.
Confirm that
OperationPAR
is set to
CC
for each transformer in the parallel group.
2.
Confirm that
OperCCBlock
is set to
Enable
for each transformer in the parallel
group.
3.
Review the setting for
CircCurrLimit
.
4.
Review the setting for
CircCurrBk
to confirm whether a circulating current limit will
result in an
Alarm
state,
Auto Block
or
Auto&Man Block
of the automatic voltage
control for tap changer, for parallel control function TR8ATCC (90).
5.
Inject a voltage V
B
equal to
VSet
for each transformer.
6.
Inject a load current for Transformer 1 that is equal to rated load current
I2Base
and
a load current for Transformer 2 that is 1% less than (
I2Base
– (
I2Base
·
CircCurrLimit))
7.
Confirm that the automatic voltage control for tap changer, for parallel control
function TR8ATCC (90) responds in accordance with the setting for
CircCurrBk
.
Alarm and blocking conditions can be confirmed through interrogation of the event
menu or the control menu on the local HMI.
VTmismatch during parallel operation
1.
Confirm that
OperationPAR
is set to
MF
for each transformer in the parallel group.
2.
Review the setting for
VTmismatch
and
tVTmismatch
.
3.
Inject a voltage V
B
equal to
VSet
for Transformer 1 and a voltage less than (
VSet
–
(
VTmismatch
·
VSet
)) for Transformer 2.
4.
This condition should result in a
VTmismatch
which will mutually block the
operation of the automatic voltage control for tap changer, parallel control function
TR8ATCC (90) for all transformers connected in the parallel group, which can be
confirmed through interrogation of the local HMI.
5.
Confirm that the automatic voltage control for tap changer, parallel control function
TR8ATCC (90) responds in accordance with the setting for
CircCurrBk
.
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
257
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...