Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are according
to the injected quantities and that ROTORANG is close to 0 rad.
For this particular injection the service values are:
•
VOLTAGE = 13.12 kV
•
CURRENT = 20918 A
•
R = 9.01%
•
X = 65.27%
•
ROTORANG = 0.04 rad
Note that these values identify a point outside the lens characteristic, even if it is close to
the point RE. Neither START nor TRIP is issued.
Execution of the dynamic test
The test may be performed by using two states of a sequence tool that is a basic feature of
test sets.
•
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance. This
is a point in the plane R-X that is far away from the lens characteristic. Define the
following three-phase symmetrical quantities (the phase angle is related to phase L1):
V
V
V
V
V
ts
t FwdZ
VT s
VT p
=
×
×
=
×
×
=
1 1
1 1 11931
0 1
13 8
95 1
.
.
.
.
.
,
,
,
EQUATION14057 V1 EN
(Equation 21)
∠
=
=
=
V
ForwardX
ForwardR
ts
arctan
arctan
.
.
59 33
8 19
82..14
°
EQUATION14058 V1 EN
(Equation 22)
frequency of V
ts
= 50 Hz
I
50s
=0 A
1MRK 504 165-UUS -
Section 11
Testing functionality by secondary injection
Transformer protection RET670 2.2 ANSI
157
Commissioning manual
Summary of Contents for RELION RET670
Page 1: ...RELION 670 SERIES Transformer protection RET670 Version 2 2 ANSI Commissioning manual...
Page 2: ......
Page 18: ...12...
Page 34: ...28...
Page 66: ...60...
Page 76: ...70...
Page 94: ...88...
Page 110: ...104...
Page 292: ...286...
Page 302: ...296...
Page 308: ...302...
Page 326: ...320...
Page 327: ...321...